| range | TeSys |
|---|---|
| product name | TeSys GV3 |
| device short name | GV3L |
| device application | Motor |
| poles description | 3P |
| network type | AC |
| utilisation category | Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 |
| network frequency | 50/60 Hz |
| breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz 50 kA Icu at 440 V AC 50/60 Hz 12 kA Icu at 500 V AC 50/60 Hz 6 kA Icu at 690 V AC 50/60 Hz 50 kA Icu at 400/415 V AC 50/60 Hz |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz 100 % at 400/415 V AC 50/60 Hz 100 % at 440 V AC 50/60 Hz 50 % at 500 V AC 50/60 Hz 50 % at 690 V AC 50/60 Hz |
| trip unit technology | Magnetic |
| magnetic tripping current | 910 A |
| fixing mode | 35 mm symmetrical DIN rail: clipped Panel: screwed (with 3 x M4 screws) |
|---|---|
| operating position | Any position |
| motor power kW | 55 kW at 690 V AC 50/60 Hz 30 kW at 400/415 V AC 50/60 Hz 37 kW at 500 V AC 50/60 Hz |
| control type | Rotary knob |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | IEC 60947-2 6 kV |
| mechanical durability | 50000 cycles |
| electrical durability | 50000 cycles for AC-3 at 415 V |
| maximum operating rate | 25 cyc/h |
| connections - terminals | EverLink BTR screw connectors 1 cable(s) 1…35 mm² solid EverLink BTR screw connectors 2 cable(s) 1…25 mm² solid EverLink BTR screw connectors 1 cable(s) 1…35 mm² flexible without cable end EverLink BTR screw connectors 2 cable(s) 1…25 mm² flexible without cable end EverLink BTR screw connectors 1 cable(s) 1…35 mm² flexible with cable end EverLink BTR screw connectors 2 cable(s) 1…25 mm² flexible with cable end |
| tightening torque | 5 N.m on EverLink BTR screw connectors for cable 25 mm² 8 N.m on EverLink BTR screw connectors for cable 35 mm² |
| mechanical robustness | Shocks: 15 Gn for 11 ms closed conforming to IEC 60068-2-27 Shocks: 30 Gn for 11 ms opened conforming to IEC 60068-2-27 Vibrations: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
| suitability for isolation | Yes conforming to IEC 60947-1 |
| height | 132 mm |
| width | 55 mm |
| depth | 136 mm |
| net weight | 0.96 kg |