| range of product | TeSys F TeSys D control relay TeSys D |
|---|---|
| range | TeSys |
| product or component type | Auxiliary contact block |
| auxiliary contacts operation | Instantaneous |
| pole contact composition | 4 NO |
| connections - terminals | Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end Screw clamp terminals 1 cable(s) 1…2.5 mm²solid with cable end Screw clamp terminals 1 cable(s) 1…2.5 mm²solid without cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²solid with cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end |
| mounting location | Front |
|---|---|
| [Ui] rated insulation voltage | 600 V - certifications UL 690 V conforming to IEC 60947-5-1 600 V - certifications CSA |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Irms rated making capacity | 140 A at <= 690 V AC conforming to IEC 60947-5-1 250 A at <= 690 V DC conforming to IEC 60947-5-1 |
| permissible short-time rating | 100 A 60 °C 1 s 120 A 60 °C 500 ms 140 A 60 °C 100 ms |
| protection type | GG fuse 10 A rating according to operational current for Ue <= 690 V |
| associated fuse rating | 10 A gG conforming to IEC 60947-5-1 |
| mechanical durability | 30 Mcycles |
| minimum switching current | 5 mA |
| minimum switching voltage | 17 V |
| non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact 1.5 ms on energisation no overlap between NC and NO contact |
| overlap time | 1.5 ms |
| insulation resistance | > 10 MOhm |
| net weight | 0.05 kg |
| environmental characteristic | Normal environment |
|---|---|
| standards | NF C 63-140 BS 4794 VDE 0660 IEC 60947-5-1 EN 60947-5-1 |
| product certifications | CSA UL |
| IP degree of protection | IP2x conforming to VDE 0106 |
| protective treatment | TH conforming to IEC 60068 |
| ambient air temperature for operation | -5…60 °C |
| ambient air temperature for storage | -60…80 °C |
| operating altitude | 3000 m without |