SCHNEIDER - ACTI9 IC60H 3P C 4A MCB

Category: ACTI9
No Referensi: A9F84304
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

Main
device application
Distribution
range
Acti 9
product name
Acti 9 iC60
product or component type
Miniature circuit-breaker
device short name
IC60H
poles description
3P
number of protected poles
3
[In] rated current
4 A
network type
AC
DC
trip unit technology
Thermal-magnetic
curve code
C
breaking capacity
10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2
70 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
utilisation category
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2
suitability for isolation
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2
standards
IEC 60947-2
IEC 60898-1
EN 60947-2
EN 60898-1
quality labels
NF
Complementary
network frequency
50/60 Hz
magnetic tripping limit
8 x In +/- 20 %
[Ics] rated service breaking capacity
70 kA 100 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
70 kA 100 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 - 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz
70 kA 100 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz
50 kA 100 % conforming to EN 60947-2 - 440 V AC 50/60 Hz
50 kA 100 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 - 125...180 V DC
15 kA 100 % conforming to EN 60947-2 - 125...180 V DC
limitation class
3 conforming to EN 60898-1
3 conforming to IEC 60898-1
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2
contact position indicator
Yes
control type
Toggle
local signalling
Trip indicator
mounting mode
Fixed
mounting support
DIN rail
comb busbar and distribution block compatibility
Top or bottom: YES