SCHNEIDER - ATV212 7.5KW 10HP 480V 3PH

No Referensi: ATV212HU75N4
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

Main
range of product
Altivar 212
product or component type
Variable speed drive
device short name
ATV212
product destination
Asynchronous motors
product specific application
Pumps and fans in HVAC
assembly style
With heat sink
network number of phases
3 phases
motor power kW
7.5 kW
motor power hp
10 hp
[Us] rated supply voltage
380...480 V - 15...10 %
supply voltage limits
323...528 V
supply frequency
50...60 Hz - 5...5 %
network frequency
47.5...63 Hz
EMC filter
Class C2 EMC filter integrated
line current
11.7 A 480 V
14.7 A 380 V
Complementary
apparent power
12.2 kVA 380 V
prospective line Isc
22 kA
continuous output current
16 A 380 V
16 A 460 V
maximum transient current
17.6 A 60 s
speed drive output frequency
0.5...200 Hz
nominal switching frequency
12 kHz
switching frequency
12...16 kHz with derating factor
6...16 kHz adjustable
speed range
1...10
speed accuracy
+/- 10 % of nominal slip 0.2 Tn to Tn
torque accuracy
+/- 15 %
transient overtorque
120 % of nominal motor torque +/- 10 % 60 s
asynchronous motor control profile
Voltage/frequency ratio, 2 points
Voltage/frequency ratio, 5 points
Flux vector control without sensor, standard
Voltage/frequency ratio - Energy Saving, quadratic U/f
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
regulation loop
Adjustable PI regulator
motor slip compensation
Adjustable
Automatic whatever the load
Not available in voltage/frequency ratio motor control
local signalling
1 LED red DC bus energized
output voltage
<= power supply voltage
isolation
Electrical between power and control
type of cable
IEC cable without mounting kit 1 45 °C copper 90 °C XLPE/EPR
IEC cable without mounting kit 1 45 °C copper 70 °C PVC
UL 508 cable with UL Type 1 kit 3 40 °C copper 75 °C PVC
electrical connection
Terminal 2.5 mm² AWG 14 VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES
Terminal 16 mm² AWG 6 L1/R, L2/S, L3/T
tightening torque
2.5 N.m 22 lb.in L1/R, L2/S, L3/T
0.6 N.m VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES
supply
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 % <= 10 A overload and short-circuit protection
Internal supply 24 V DC 21...27 V <= 200 A overload and short-circuit protection
analogue input number
2
analogue input type
Switch-configurable voltage VIA 0...10 V DC 24 V max 30000 Ohm 10 bits
Configurable voltage VIB 0...10 V DC 24 V max 30000 Ohm 10 bits
Configurable PTC probe VIB 0...6 probes 1500 Ohm
Switch-configurable current VIA 0...20 mA 250 Ohm 10 bits
sampling duration
2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analog
response time
2 ms +/- 0.5 ms FM analog
7 ms +/- 0.5 ms FLA, FLC discrete
7 ms +/- 0.5 ms FLB, FLC discrete
7 ms +/- 0.5 ms RY, RC discrete
accuracy
+/- 0.6 % VIA for a temperature variation 60 °C
+/- 0.6 % VIB for a temperature variation 60 °C
+/- 1 % FM for a temperature variation 60 °C
linearity error
+/- 0.15 % of maximum value input VIA
+/- 0.15 % of maximum value input VIB
+/- 0.2 % output FM
analogue output number
1
analogue output type
Switch-configurable voltage FM 0...10 V DC 7620 Ohm 10 bits
Switch-configurable current FM 0...20 mA 970 Ohm 10 bits
discrete output number
2
discrete output type
Configurable relay logic FLA, FLC NO 100000 cycles
Configurable relay logic FLB, FLC NC 100000 cycles
Configurable relay logic RY, RC NO 100000 cycles
minimum switching current
3 mA 24 V DC configurable relay logic
maximum switching current
5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R
5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R
2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R
2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R
discrete input type
Programmable F 24 V DC level 1 PLC 4700 Ohm
Programmable R 24 V DC level 1 PLC 4700 Ohm
Programmable RES 24 V DC level 1 PLC 4700 Ohm
discrete input logic
Positive logic (source) F, R, RES <= 5 V >= 11 V
Negative logic (sink) F, R, RES >= 16 V <= 10 V
acceleration and deceleration ramps
Automatic based on the load
Linear adjustable separately from 0.01 to 3200 s
braking to standstill
By DC injection
protection type
Motor phase break motor
Break on the control circuit drive
Thermal power stage drive
Overvoltages on the DC bus drive
Against exceeding limit speed drive
Against input phase loss drive
With PTC probes motor
Input phase breaks drive
Line supply overvoltage and undervoltage drive
Line supply undervoltage drive
Overcurrent between output phases and earth drive
Overheating protection drive
Short-circuit between motor phases drive
Thermal protection motor
dielectric strength
3535 V DC between earth and power terminals
5092 V DC between control and power terminals
insulation resistance
>= 1 MOhm 500 V DC for 1 minute
frequency resolution
0.024/50 Hz analog input
0.1 Hz display unit
communication port protocol
APOGEE FLN
BACnet
LonWorks
METASYS N2
Modbus
connector type
1 RJ45
1 open style
physical interface
2-wire RS 485
transmission frame
RTU
transmission rate
9600 bps or 19200 bps
data format
8 bits, 1 stop, odd even or no configurable parity
type of polarization
No impedance
number of addresses
1...247
communication service
Monitoring inhibitable
Read device identification (43)
Read holding registers (03) 2 words maximum
Time out setting from 0.1 to 100 s
Write multiple registers (16) 2 words maximum
Write single register (06)
option card
Communication card LonWorks
operating position
Vertical +/- 10 degree
width
180 mm
height
232 mm
depth
170 mm
product weight
6.45 kg
power dissipation in W
291 W
air flow
100 m3/h
functionality
Mid
specific application
HVAC
IP degree of protection
IP21
Variable speed drive application selection
Building - HVAC : compressor for scroll
Building - HVAC : fan
Building - HVAC : pump
Motor power range AC-3
7...11 kW at 380...440 V 3 phases
7...11 kW at 480...500 V 3 phases
motor starter type
Variable speed drive
Environment
electromagnetic compatibility
Conducted radio-frequency immunity test level 3 IEC 61000-4-6
Voltage dips and interruptions immunity test IEC 61000-4-11
1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5
Electrical fast transient/burst immunity test level 4 IEC 61000-4-4
Electrostatic discharge immunity test level 3 IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3
pollution degree
3 IEC 61800-5-1
IP degree of protection
IP20 on upper part without blanking plate on cover EN/IEC 61800-5-1
IP20 on upper part without blanking plate on cover EN/IEC 60529
IP21 EN/IEC 61800-5-1
IP21 EN/IEC 60529
IP41 on upper part EN/IEC 61800-5-1
IP41 on upper part EN/IEC 60529
vibration resistance
1 gn 13...200 Hz EN/IEC 60068-2-8
1.5 mm 3...13 Hz EN/IEC 60068-2-6
shock resistance
15 gn 11 ms IEC 60068-2-27
environmental characteristic
Classes 3C1 IEC 60721-3-3
Classes 3S2 IEC 60721-3-3
noise level
51 dB 86/188/EEC
operating altitude
1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m
<= 1000 m without derating
relative humidity
5...95 % without condensation IEC 60068-2-3
5...95 % without dripping water IEC 60068-2-3
ambient air temperature for operation
-10...40 °C without derating
> 40...50 °C with derating factor
ambient air temperature for storage
-25...70 °C
standards
EN 55011 class A group 1
EN 61800-3
EN 61800-3 category C2
EN 61800-3 category C3
EN 61800-3 environments 1 category C1
EN 61800-3 environments 1 category C2
EN 61800-3 environments 1 category C3
EN 61800-3 environments 2 category C1
EN 61800-3 environments 2 category C2
EN 61800-3 environments 2 category C3
EN 61800-5-1
IEC 61800-3
IEC 61800-3 category C2
IEC 61800-3 category C3
IEC 61800-3 environments 1 category C1
IEC 61800-3 environments 1 category C2
IEC 61800-3 environments 1 category C3
IEC 61800-3 environments 2 category C1
IEC 61800-3 environments 2 category C2
IEC 61800-3 environments 2 category C3
IEC 61800-5-1
UL Type 1
product certifications
CSA
C-Tick
NOM 117
UL
marking
CE