| range | TeSys |
|---|---|
| product name | TeSys LC1D.K |
| product or component type | Capacitor duty contactor |
| device short name | LC1DFK |
| device application | Control |
| contactor application | Power factor correction |
| poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | <= 690 V AC 50/60 Hz for power circuit |
| reactive power rating | 7 kvar at 220...240 V AC 50/60 Hz <= 55 °C 13 kvar at 400...440 V AC 50/60 Hz <= 55 °C 21 kvar at 660...690 V AC 50/60 Hz <= 55 °C |
| control circuit type | AC 50/60 Hz |
| [Uc] control circuit voltage | 220 V AC 50/60 Hz |
| auxiliary contact composition | 1 NO + 2 NC instantaneous for control circuit |
| electrical durability | 300000 cycles at Ue 400 V 200000 cycles at Ue 690 V |
| mounting support | DIN rail Plate |
| standards | IEC 60947-4-1 |
| product certifications | CCC CSA UL |
| connections - terminals | Power circuit : connector 1 cable(s) 2.5 mm² - cable stiffness: flexible - with cable end Power circuit : connector 2 cable(s) 1.5 mm² - cable stiffness: flexible - with cable end Power circuit : connector 1 cable(s) 4 mm² - cable stiffness: solid - without cable end Power circuit : connector 2 cable(s) 4 mm² - cable stiffness: solid - without cable end |
| tightening torque | Power circuit : 1.7 N.m - on connector |
| operating rate | 240 cyc/h |
| auxiliary contacts type | Type mechanically linked (1 NO + 2 NC) conforming to IEC 60947-5-1 |
|---|
| IP degree of protection | IP20 conforming to IEC 60529 |
|---|---|
| protective treatment | TH conforming to IEC 60068-2-30 |
| ambient air temperature for operation | -5...60 °C |
| ambient air temperature for storage | -60...80 °C |
| operating altitude | 3000 m without derating |
| height | 130 mm |
| width | 45 mm |
| depth | 117 mm |
| product weight | 0.53 kg |