SCHNEIDER - CVS160F TM160D 4P3D

Category: EASYPACT CVS
No Referensi: LV516343
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

Main
range of product
Easypact CVS100...250
product or component type
Circuit breaker
device short name
CVS160F
device application
Distribution
poles description
4P
protected poles description
3d
neutral position
Left
Earth leakage protection (Vigi add on)
Without
[In] rated current
160 A ( 40 °C )
breaking capacity code
F
network type
AC
[Icu] Breaking capacity
36 kA Icu conforming to IEC 60947-2 at 440 V AC 50/60 Hz
36 kA Icu conforming to IEC 60947-2 at 380/415 V AC 50/60 Hz
70 kA Icu conforming to IEC 60947-2 at 220/240 V AC 50/60 Hz
utilisation category
Category A
trip unit name
TM-D
trip unit technology
Thermal-magnetic
trip unit rating
160 A ( 40 °C )
protection type
Overload protection (thermal)
Short-circuit protection (magnetic)
Complementary
network frequency
50/60 Hz
control type
Toggle
mounting mode
Fixed
mounting support
Backplate
upside connection
Front
downside connection
Front
connections - terminals
Screw connection
[Uimp] rated impulse withstand voltage
8 kV conforming to EN/IEC 60947-2
thermal protection adjustment range
112...160 A
[Ics] rated service breaking capacity
18 kA conforming to IEC 60947-2 440 V AC 50/60 Hz
36 kA conforming to IEC 60947-2 380/415 V AC 50/60 Hz
70 kA conforming to IEC 60947-2 220/240 V AC 50/60 Hz
mechanical durability
25000 cycles
electrical durability
12000 cycles conforming to IEC 60947-2 415 V In
connection pitch
35 mm
contact position indicator
Yes
neutral protection setting
No protection 3d
long time pick-up adjustment type Ir
Adjustable
long time pick-up adjustment range
0.7...1 x In
long time delay adjustment type
Fixed
instantaneous pick-up adjustment type Ii
Fixed
instantaneous pick-up adjustment range
1250 A
height
161 mm
width
140 mm
depth
86 mm
product weight
2.3 kg
Environment
electrical shock protection class
Class II
standards
EN 60947-2
IEC 60947-2
product certifications
GOST
IEC
IP degree of protection
IP40
ambient air temperature for operation
-25...70 °C
ambient air temperature for storage
-50...85 °C