range | TeSys |
---|---|
product name | TeSys LRD |
product or component type | Differential thermal overload relay |
device short name | LRD |
relay application | Motor protection |
product compatibility | LC1D40A LC1D50A LC1D65A |
network type | AC DC |
thermal protection adjustment range | 23...32 A |
[Ui] rated insulation voltage | 600 V power circuit conforming to CSA 600 V power circuit conforming to UL 690 V power circuit conforming to IEC 60947-4-1 |
network frequency | 0...400 Hz |
---|---|
mounting support | Plate with specific accessories Rail with specific accessories Under contactor |
tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
[Ith] conventional free air thermal current | 5 A for signalling circuit |
permissible current | 0.95 A at 380 V AC-15 for signalling circuit 0.06 A at 440 V DC-13 for signalling circuit |
[Ue] rated operational voltage | 690 V AC 0...400 Hz |
[Uimp] rated impulse withstand voltage | 6 kV |
phase failure sensitivity | Tripping current 130 % of Ir on two phase, the last one at 0 |
control type | Red push-button stop Blue push-button for reset mode |
temperature compensation | -20...60 °C |
connections - terminals | Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² flexible without cable end Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² flexible with cable end Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² solid without cable end Power circuit : EverLink BTR screw connectors 1 cable(s) 1...35 mm² flexible without cable end Power circuit : EverLink BTR screw connectors 1 cable(s) 1...35 mm² flexible with cable end Power circuit : EverLink BTR screw connectors 1 cable(s) 1...35 mm² solid without cable end |
tightening torque | Control circuit : 1.7 N.m on screw clamp terminals Power circuit : 5 N.m on EverLink BTR screw connectors |
height | 123 mm |
width | 55 mm |
depth | 123 mm |
product weight | 0.375 kg |
protective treatment | TH conforming to IEC 60068 |
---|---|
IP degree of protection | IP20 conforming to IEC 60529 |
ambient air temperature for operation | -20...60 °C without derating conforming to IEC 60947-4-1 |
ambient air temperature for storage | -60...70 °C |
flame retardance | V1 conforming to UL 94 |
mechanical robustness | Shocks 15 Gn for 11 ms IEC 60068-2-7 Vibrations 4 gn IEC 60068-2-6 |
dielectric strength | 6 kV at 50 Hz conforming to IEC 60255-5 |
standards | ATEX D 94/9/CE EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14 |
product certifications | ATEX INERIS BV CCC CSA DNV GL GOST LROS (Lloyds register of shipping) RINA UL |