Tokopedia:

Selector switch - Ø22 - standard handle - 3 positions - 2NO

 

Main
range of product
Harmony Easy XA2
product or component type
Complete selector switch
device short name
XA2
bezel material
Plastic
mounting diameter
22 mm
Complementary
sale per indivisible quantity
1
fixing center
>= 30 x 40 mm (panel) - thickness: 1…5 mm
fixing mode
Fixing nut: 2…2.4 N.m
shape of signaling unit head
Round
type of operator
stay put
operator profile
Black standard handle
operator position information
3 positions
contacts type and composition
2 NO
contact operation
Slow-break
mechanical durability
300000 cycles
connections - terminals
, clamping capacity: <= 2 x 1.5 mm²
, clamping capacity: <= 1 x 2.5 mm²
, clamping capacity: >= 1 x 0.5 mm²
Faston terminals, connection size: 6.3 mm
tightening torque
0.8 N.m
short-circuit protection
10 A fuse type gL conforming to IEC 60269-1
[Ith] conventional free air thermal current
10 A (screw-clamp terminals)
[Ui] rated insulation voltage
600 V conforming to EN 60947-1
[Uimp] rated impulse withstand voltage
EN 60947-1 6 kV
[Ie] rated operational current
3 A at 240 V, AC-15, A600
0.27 A at 250 V, DC-13, Q600
electrical durability
500000 cycles, AC-15, 3 A at 230 V, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-4
500000 cycles, DC-13, 0.2 A at 110 V, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-4
electrical reliability
Λ < 10exp(-8) at 24 V
width
30 mm
height
42 mm
depth
68.2 mm
net weight
0.054 kg
Environment
protective treatment
TC
ambient air temperature for storage
-40…70 °C
ambient air temperature for operation
-25…55 °C
overvoltage category
Class I conforming to IEC 536
IP degree of protection
IP65 conforming to IEC 60529
IK degree of protection
IK06 conforming to IEC 60529
standards
GB 14048.1
GB 14048.5
IEC 60947-5-1
IEC 60947-1
product certifications
CCC
CE
vibration resistance
10 gn (f= 40…500 Hz) conforming to IEC 60068-2-6
shock resistance
120 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27