SCHNEIDER - XT 14 I-O 100-240 VAC

Category: ZELIO LOGIC
No Referensi: SR3XT141FU
HUBUNGI KAMI

Call / Whatsapp:


Whatsapp Only:


Tokopedia:

Discrete I/O extension module - 14 I O - 100..240 V AC - for Zelio Logic

 

Main
range of product
Zelio Logic
product or component type
Discrete I/O extension module
Complementary
number or control scheme lines
120 with ladder programming
cycle time
6…90 ms
backup time
10 years at 25 °C
clock drift
12 min/year at 0…55 °C
checks
Program memory on each power up
[Us] rated supply voltage
100...240 V AC
supply voltage limits
85…264 V
supply frequency
50/60 Hz
reverse polarity protection
With
discrete input number
8
discrete input voltage
100...240 V AC
discrete input current
0.6 mA
discrete input frequency
57...63 Hz
47...53 Hz
voltage state 1 guaranteed
>= 79 V for discrete input
voltage state 0 guaranteed
<= 40 V for discrete input
current state 1 guaranteed
>= 0.17 mA (discrete input)
current state 0 guaranteed
<= 0.5 mA (discrete input)
input impedance
350 kOhm for discrete input
number of outputs
6 relay
output voltage limits
5...30 V DC (relay output)
24...250 V AC
contacts type and composition
NO for relay output
output thermal current
5 A for 2 outputs for relay output
8 A for 4 outputs for relay output
electrical durability
AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to EN/IEC 60947-5-1
AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1
DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to EN/IEC 60947-5-1
DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1
switching capacity in mA
>= 10 mA at 12 V (relay output)
operating rate in Hz
0.1 Hz (at Ie) for relay output
10 Hz (no load) for relay output
mechanical durability
10000000 cycles for relay output
[Uimp] rated impulse withstand voltage
4 kV EN/IEC 60947-1 and EN/IEC 60664-1
response time
50 ms with ladder programming (from state 0 to state 1) for discrete input
50 ms with ladder programming (from state 1 to state 0) for discrete input
50...255 ms with FBD programming (from state 0 to state 1) for discrete input
50...255 ms with FBD programming (from state 1 to state 0) for discrete input
10 ms (from state 0 to state 1) for relay output
5 ms (from state 1 to state 0) for relay output
connections - terminals
Screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) solid
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) solid
tightening torque
0.5 N.m
overvoltage category
III conforming to EN/IEC 60664-1
net weight
0.22 kg
Environment
product certifications
C-Tick
GOST
CSA
GL
UL
standards
EN/IEC 61000-4-6 level 3
EN/IEC 61000-4-2 level 3
EN/IEC 61000-4-4 level 3
EN/IEC 60068-2-27 Ea
EN/IEC 61000-4-5
EN/IEC 61000-4-11
EN/IEC 60068-2-6 Fc
EN/IEC 61000-4-12
EN/IEC 61000-4-3
IP degree of protection
IP20 (terminal block) conforming to IEC 60529
IP40 (front panel) conforming to IEC 60529
environmental characteristic
EMC directive conforming to EN/IEC 61000-6-2
EMC directive conforming to EN/IEC 61000-6-3
EMC directive conforming to EN/IEC 61000-6-4
EMC directive conforming to EN/IEC 61131-2 zone B
Low voltage directive conforming to EN/IEC 61131-2
disturbance radiated/conducted
Class B conforming to EN 55022-11 group 1
pollution degree
2 conforming to EN/IEC 61131-2
ambient air temperature for operation
-20…40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2
-20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2
ambient air temperature for storage
-40…70 °C
operating altitude
2000 m
maximum altitude transport
3048 m
relative humidity
95 % without condensation or dripping water