| range of product | Harmony XB7 |
|---|---|
| product or component type | Push-button |
| device short name | XB7 |
| mounting diameter | 22 mm |
| sale per indivisible quantity | 10 |
| IP degree of protection | IP20 (rear face) conforming to IEC 60529 IP65 (front face) conforming to IEC 60529 |
| shape of signaling unit head | Round |
| type of operator | spring return |
| operator profile | Red flush, unmarked |
| contacts type and composition | 1 NC |
| connections - terminals | Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1 Screw clamp terminals, 1 x 0.34...2 x 2.5 mm² without cable end conforming to EN/IEC 60947-1 |
| device presentation | Monolithic product |
| CAD overall width | 29 mm |
|---|---|
| CAD overall height | 29 mm |
| CAD overall depth | 51.5 mm |
| terminals description ISO n°1 | (11-12)NC |
| net weight | 0.021 kg |
| device mounting | Fixing hole - diameter: 22.5 mm 22.3 +0.4/0 conforming to EN/IEC 60947-1 |
| fixing center | >= 30 x 40 mm (support panel) metal - thickness: 1…6 mm >= 30 x 40 mm (support panel) plastic - thickness: 2…6 mm |
| fixing mode | Fixing nut beneath head: 2…2.4 N.m |
| contact operation | Slow-break |
| positive opening | With NC contact conforming to EN/IEC 60947-5-1 appendix K |
| mechanical durability | 1000000 cycles |
| tightening torque | 0.8…1.2 N.m conforming to EN 60947-1 |
| shape of screw head | Cross compatible with JIS No 1 screwdriver Cross compatible with Philips no 1 screwdriver Cross compatible with pozidriv No 1 screwdriver Slotted compatible with flat Ø 4 mm screwdriver Slotted compatible with flat Ø 5.5 mm screwdriver |
| short-circuit protection | 4 A cartridge fuse type gG conforming to EN/IEC 60947-5-1 |
| [Ui] rated insulation voltage | 250 V (pollution degree 3) conforming to EN/IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | EN/IEC 60947-1 4 kV |
| [Ie] rated operational current | 0.1 A at 250 V, DC-13, R300 conforming to EN/IEC 60947-5-1 0.22 A at 125 V, DC-13, R300 conforming to EN/IEC 60947-5-1 0.3 A at 240 V, AC-14, D300 conforming to EN/IEC 60947-5-1 0.6 A at 120 V, AC-14, D300 conforming to EN/IEC 60947-5-1 |
| electrical durability | 1000000 cycles, DC-13, 0.3 A at 24 V, operating rate <216000 cyc/mn, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 0.03 A at 230 V, operating rate <216000 cyc/mn, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 0.09 A at 240 V, operating rate <108000 cyc/mn, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C |
| electrical reliability | Λ <= 10exp(-6) at 17 V, 5 mA conforming to EN/IEC 60947-5-4 |